Full Description
Description
This is a combined synopsis/solicitation for commercial products and commercial services
prepared in accordance with the format in Federal Acquisition Regulation (FAR) subpart 12.6, Streamlined Procedures for Evaluation and Solicitation for Commercial Products and
Commercial Services, as supplemented with additional information included in this notice. This
announcement constitutes the only solicitation; quotes are being requested, and a written
solicitation document will not be issued. This solicitation is issued as an RFQ. The solicitation document and incorporated provisions
and clauses are those in effect through Federal Acquisition Circular (FAC) 2025-06 can be
found at Acquisition.gov. This solicitation is set-aside for Small Business. The associated North American Industrial Classification System (NAICS) code for this
procurement is 561621 Security Systems Services (except Locksmiths, with a small business size standard of $25.0M. The FSC/PSC is H163 Quality Control- Alarm, Signal, and Security Detection Systems. The Boston Healthcare System, Brockton Division is seeking In-Patient Behavioral Health Door Alarm Test and Certification services. All interested companies shall provide quotations for the following: Services
Item Number
Description
Quantity
Unit Unit Price
Amount
0001
Base Year: 114 MH Overdoor Alarms 6 Alarm Controllers Quarterly Testing (3) Annual Certification (1)
4
EA 1001
Option Year 1: 114 MH Overdoor Alarms 6 Alarm Controllers Quarterly Testing (3) Annual Certification (1)
4
EA 2001
Option Year 2: 114 MH Overdoor Alarms 6 Alarm Controllers Quarterly Testing (3) Annual Certification (1)
4
EA 3001
Option Year 3: 114 MH Overdoor Alarms 6 Alarm Controllers Quarterly Testing (3) Annual Certification (1)
4
EA 4001
Option Year 4: 114 MH Overdoor Alarms 6 Alarm Controllers Quarterly Testing (3) Annual Certification (1)
4
EA Total $ Performance Work Statement In-Patient Behavioral Health Door Alarm Test and Certification Introduction. The VHA Boston Healthcare System (VHA BHS), Brockton Campus, located at 940 Belmont Street, Brockton, MA 02301 has a requirement to provide quarterly testing and annual inspection/recertification of The Door Switch suicide prevention door alarm systems installed in six (6) in-patient behavioral health wards in Building 2 of the VHA BHS Brockton Campus for the next 5 years. The six (6) behavioral health wards are as follows: Behavioral Health Ward
System Control Panels
System Door Alarms
Ward 2-1-B
1
16 Doors
Ward 2-2-B
1
20 Doors
Ward 2-3-B
1
20 Doors
Ward 2-3-C
1
20 Doors
Ward 2-4-B
1
20 Doors
Ward 2-2-C
1
18 Doors Description / Scope / Objective. The Contractor must provide all labor, equipment, tools, material, supervision and other items and services necessary to perform the work as defined in this Performance Work Statement.
Applicable Documents.
3.1. The following laws, regulations, policies, and procedures in effect on date of contract issuance and all subsequent changes or updates apply:
FAR
Federal Acquisition Regulation
VAAR
Veterans Administration Acquisition Regulation
VA Directives, Design Manuals, Master Specs
https://www.cfm.va.gov/til/ ASME
American Society of Mechanical Engineers
OSHA
Occupational Safety and Health Administration
SCA DOL Website
Service Contract Act (SCA) Directory of Occupations (Fifth Edition) http://www.dol.gov/whd/contracts/sca.htm 3.2. Glossary. Acronyms used in this PWS are listed below for easy reference: CO Contracting Officer
COR Contracting Officer s Representative FAR Federal Acquisition Regulation OEM Original Equipment Manufacturer Performance Requirements. 4.1. One (1) base year with four (4) one-year option periods
4.1.1. Quarterly testing of six (6) The Door Switch suicide prevention door alarm systems installed in Building 2, Behavioral Health Wards 2-1-B, 2-2-B, 2-2-C, 2-3-B, 2-3-C, and 2-4-B of the VHA BHS Brockton campus consisting of six (6) system control panels and 114 door alarms. Once every quarter, the contractor shall visit Building 2 of the VHA BHS Brockton campus and conduct a Walk and Press Test and an event download of each system. The Walk and Press Test consists of the following:
4.1.1.1. Please read all of the following instructions prior to initiating a walk and press test.
4.1.1.2. Locate the Silent Testing Keypad, in the nurses station above the 6160 Door Switch Keypad.
4.1.1.3. Second person should be standing at the first door to be tested, with mobile phone or radio.
4.1.1.4. At the Silent Testing Keypad enter 4321*- Indicator will turn from Red to Green.
4.1.1.5. The audible alarms are now silenced for 99 seconds.
4.1.1.6. Staff member located at the door can now press actuator on top of door (<2 pounds of pressure to activate)
4.1.1.7. Strobe above door should signal, the keypad in the nurses station should beep continuously and display the room and zone number.
4.1.1.8. Once confirmed, Staff member at door can use key to disarm beeping in nurses station via keyswitch at the