Defense Supply Center Richmond B46 Generator Tie In
Department
DEPT OF DEFENSE.DEFENSE LOGISTICS AGENCY.DCSO.DCSO RICHMOND.DCSO RICHMOND DIVISION #1
Country
United States
Closing Date
Not specified
Estimated Value
Not disclosed
Summary
DEPT OF DEFENSE.DEFENSE LOGISTICS AGENCY.DCSO.DCSO RICHMOND.DCSO RICHMOND DIVISION #1 is seeking Defense Supply Center Richmond B46 Generator Tie In. Update 22 May 2026: There appears to be a conflict between the one-line diagram on Sheet E-602 and the new work power plan on Sheet E-110 regarding the secondary feeder from XFMR T58 to ATS-B. Location: VA.
Full Description
Update 22 May 2026: There appears to be a conflict between the one-line diagram on Sheet E-602 and the new work power plan on Sheet E-110 regarding the secondary feeder from XFMR T58 to ATS-B. On E-602, this feeder is identified as 3200.4 (9 sets of 4-#500 KCMIL, 4" conduit), which per the feeder schedule appears to indicate new conduit installation. However, Sheet E-110 references Keynote 2 along the same routing, which directs conductors to be installed within existing underground conduits, consistent with the parallel T57-to-ATS-A feeder identified as 3200.4U. Please confirm whether the T58-to-ATS-B feeder is intended to: Reuse existing underground conduit infrastructure, in which case the feeder designation should read 3200.4U; or Be installed in new conduit, in which case Keynote 2 would not apply to this feeder run. Answer: The intent is to reuse the existing conduit infrastructure for the T58 to ATS-B feeder. That feeder on E-602 should have been identified as 3200.4U. RFI's: All building power outages are to take place on weekends, holiday breaks, or times when there will be no occupants in the building. Correct. As this building will be occupied, we cannot have power interruptions during normal working hours. Please confirm per the site visit comments - Contractor is not required to provide backup generators or backup power for weekend outages to take place. Confirmed. The contractor is not required to provide a backup generator or power for weekend outages. ------------ Update: Revised Attachment 1 - Plans attached. See redaction on page E-001 removing specific language about the portable generator. ------------ Continuation Page Defense Supply Center Richmond (DSCR) Generator Tie In This is a solicitation for construction prepared in accordance with the format in FAR Part 14 and FAR Part 36, as supplemented with additional information included in this notice. The solicitation number SP4703-26-B-0001 is issued as an Invitation for Bid (IFB). The resulting contract will be a firm-fixed price award with an expected Period of Performance of 365 days from the issuance of the Notice to Proceed. This acquisition is set-aside for 100% small businesses. The North American Industry Classification System (NAICS) Code is 238210 (Electrical Contractors) . The small business size standard is $19M. DEPARTMENT OF LABOR WAGE DECISION (CONSTRUCTION) Any contract awarded as a result of this solicitation will be subject to the U.S. Department of Labor Wage Decision(s) Number VA20260007 01/02/2026 . For an offer to be considered for award, the contractor must have a physical office from which mobilization occurs within 120 miles to Defense Supply Center Richmond, 6090 Strathmore Road , Richmond, VA 23237 . This shall be listed clearly in the bid. The contractor must be registered in the System for Award Management (SAM) prior to award. If not already registered in SAM, go to the SAM website www.sam.gov to register prior to submitting your bid. Site Visit for this requirement will be May 14, 2026 at 10:00 AM . Questions are due on May 15, 2026, end of day. Submit questions via email to Brandon.Jump@dla.mil. Bids are due on May 26, 2026, 11:59PM. Bids shall be delivered via DOD SAFE by the deadline. The interested party MUST contact the Contract Specialist by (and no later than) 12:00 (noon) Eastern Time one day prior to the Bid Due Date, so that the Contract Specialist can issue the Drop Off Request to the interested party. Use the “Drop Off” icon and set the Contract Specialist email as the recipient. You may also add the Contracting Officer email as a secondary recipient email. After you have submitted the Drop-Off, you will receive a confirmation email timestamping your submission. Save this email for your records. Do not send your bid to the Government more than five days ahead of the closing date. The retrieval link is only valid for seven days. Access to Defense Supply Center Richmond is dictated by the language at the following location: https://www.dla.mil/Aviation/Installation/Visitors-and-ID-Office/ The screening system will require visitors and contractors to pre-enroll in DBIDS (Defense Biometric Identification System). 
Want tenders like this emailed daily?
Get matched government contracts for your industry every morning. Free forever, with plain-English summaries and direct bid links.
Sign Up FreeSimilar Tenders
TTUS Construction Manager-Agent (CMA) 3 Year Pre-Qualification 2026-2029 RFQ
768Closes May 26, 2026
LACDA26-055 - SENIOR GRANT PROGRAM CONSTRUCTION REHABILITATION SERVICES-SG22-...
Los Angeles CountyCloses May 26, 2026
Owner's Representative RFQ
Lacey Fire District 3Closes May 26, 2026
On Call Construction Estimating
Seattle Housing AuthorityCloses May 26, 2026
VET SERVICE FOR LEC
Department of AgricultureCloses May 27, 2026